ENG_23KV_GIS_IED


T-IED 23kV
T-IED 23kV has total functions for metering, monitoring, control, protection, and interlock, which are needed for substation automation based on IEC61850. It’s available to be various and flexible engineering with high speed PLC functions for the protective functions . For DI/DO point, it’s possible to check more conditions and control output By choosing the expanded structure. T-IED23kV is the next generation power monitoring and protection device to manage the power system much more conveniently by embedding IEC61850 communication, PLC logic and other functions. Main Functions
- Substation automation IED
- Saved accident waveform
- Changeable logic(PLC)
- Supported IEC61850 protocol
- Various measurement
- Control the circuit breaker
- Embedded digital filter(DFT)
- Various monitoring functions
- Real time analysis for Vector
- Analysis for Event
Applied to Korean Electric Power Corporation general standard.(KEPCO)
- A25GS-5945-002102000 Overvoltage IED (GS-5945-0021) - [13-11-30]
- A25GS-5945-002403000 Reclosing Overcurrent protection IED (GS-5945-0024) - [17.1]
- A25GS-5945-002503000 25.8kV Overcurrent protection IED (GS-5945-0025) - [17.1]
- A25GS-5945-002602000 Undervoltage protection IED (GS-5945-0026) - [13-11-30]
Protective relay
ITEM Contents
Unbalance over current Protection UBOC(46)
Inst. Over Current Protection OCR(50)
Time Over Current Protection OCR(51)
Inst. Over Current Ground Protection OCGR(50N)
Time Over Current Ground Protection OCGR(51N)
Under Frequency Protection UFR(81U)
Reclosing Protection RCS(79)
Over Voltage Protection OVR(59)
Under Voltage Projection UVR(27)
Measurement
ITEM Range Precision Remark
Voltage 0.0 ~ 999.99KV ±0.2% VZA,B,CN, Vpos, Vneg
Current 0.0 ~ 999.99KA ±0.2% IA,B,CN, Ipos, Ineg, Iavg
Active Power 0.0 ~ 999.99MW ±1% A, B, C, 3P
Reactive Power 0.0 ~ 999.99MVAR ±1% A, B, C, 3P
Apparent power 0.0 ~ 999.99MVA ±1% A, B, C, 3P
Active Energy 0.00 ~ 9999.99MWH ±1% A, B, C, 3P
Reactive Energy 0.00 ~ 9999.99MVARH ±1% A, B, C, 3P
Frequency 45 ~ 65Hz ±0.02Hz
Power Factor(PF) -1.000 ~ 1.000 ±1% A, B, C, 3P
Record
Item Contents Remark
Event log(1024 event) Log Log in/out
System Value change, reset
DI/DO Digital I/O
Protection function operation Trip, Pickup, ...
Fault current
Fault log(1024 event)
Fault wave
User setting trigger point
Available to set the location of Trigger.
Available to set the number of save cycles (Before/After)
Save the value of Current, Voltage, etc. and the timing.
Save COMTRADE format
Support fault wave view from Manager
General Spec. (1)

Item Contents
Input Rated Frequency 50/60 Hz
Rated Voltage PT AC110V/√3, 8ch(A/B bus)
Rated Current CT 5A, 4ch
Rated Control Power DC 125V(±20%)
Digital Input DC 125V 60points
Output POWER 16 points(Normal Open)
Operating temperature range -25℃ ~ + 55℃
Relative humidity 10% ~ 100%
Altitude Under altitude of 1,000m
Remark The position without abnormal vibration and any shock.
Communication IEC61850-1~10
General Spec. (2)

Item Contents
CT/PT Module CT - 4ch
PT - 8ch
Relay 50, 51, 50N, 51N, 46(UBOC), 671, 67D, 67NI, 67ND, 81U, 25
Input / Output DO - 16EA
DI - 60EA
Current / Voltage Ia, Ib, Ic, I1, I2, I0
A BUS : Va, Vb, Vc, Vn, V1, V2, V0, Vab, Vbc, Vca
B BUS : Va, Vb, Vc, Vn, V1, V2, V0, Vab, Vbc, Vca
Power & Frequency S, P, Q, PF, Frequency, kWh (Forward / Reverse),
Kvarh (Forward / Reverse )
Real Time Monitoring Vector diagrams
I/O Monitoring Digital Input & Digital Output
Goose Sub, Goose Sub Q
PLC M, S Logic Conditions
Event & Fault Wave Recorder Event - 1000 EA
Fault wave - 12 EA
Communication IEC61850 MMS & GOOSE Service
Logic Ourselves PLC logic structure